Profile
The tasks of the working group are legally regulated and industrial metrology. The background to this is on the one hand the reliability of the transmission of electrical energy from the generator to the consumer and on the other hand the precise calculation of the energy consumption at high voltages and currents.
Research/Development
The working group researches and develops new measurement methods, automated measurement data acquisition and measurement devices in the fields of conventional and non-conventional measurement transformers as well as high-voltage measurement and generation devices. Furthermore, the working group participates in current topics of instrument transformer and high voltage technology in the context of national and international research projects. Part of this is technical cooperation with other countries to set up or improve metrology.
Services
The service area of the working group includes tests and calibrations of high-voltage measuring devices, instrument transformers, converter measuring devices, burdens, and burden measuring devices for the accredited test centers for measuring devices for electricity and other applicants. Furthermore, the support of test centers for measuring devices for electricity and the accredited calibration laboratories of the German Accreditation Body (DAkkS) is the responsibility of the working group.
Calibration System for Lightning Impulse and Switching Impulse Test Sets

Short Name | LI / LIC / SI | |
Principle | Comparision Method | |
rel. ext. (k=2) Measurement Uncertainty | 0,3 % up to 0,5 % for Û 1 % up to 2 % for Time Parameter | |
Measuring Conditions | 10 V up to 1500 kV
|
Calibrator for Step Voltage

Short Name | Step Voltage | |
Principle | Step Method | |
rel. ext. (k=2) Measurement Uncertainty | 5 % for Overshoot 5 ns up to 20 ns for Time Parameter | |
Measuring Conditions | 1 % up to 5 % overshoot |
Calibrator for Impulse Current

Short Name | Impulse Current | |
Principle | Comparision Method | |
rel. ext. (k=2) Measurement Uncertainty | 0,5 % up to 0,6 % for Î 1,3 % up to 1,5 % for Time Parameter | |
Measuring Conditions | 50 A up to 20 kA |
Calibrator for High Voltage (HVAC)

Short Name | HVAC | |
Principle | Comparision Method | |
rel. ext. (k=2) Measurement Uncertainty | 5·10-5 bis 1·10-4 | |
Measuring Conditions | 1 kV up to 800 kV
|
Calibrator for High Voltage (HVDC)

Short Name | HVDC | |
Principle | Comparision Method | |
rel. ext. (k=2) Measurement Uncertainty | 2·10-6 up to 100·10-6 | |
Measuring Conditions | up to ±400 kV
|
Calibrator for Partial Discharge Test Sets

Short Name | TE | |
Principle | Direct Method | |
rel. ext. (k=2) Measurement Uncertainty | (0.2 + 0.02q), q in pC | |
Measuring Conditions | 1 pC up to 5000 pC
|
Calibrator for Loss Factor Test Sets

Short Name | tan (δ) | |
Principle | Comparision Method | |
rel. ext. (k=2) Measurement Uncertainty | 1·10-5 up to 1·10-3 | |
Measuring Conditions | 1 pF up to 1000 pF For Low-Voltage: For High-Voltage:
|
Calibrator for Capacity

Short Name | C | |
Principle | Comparision Method | |
rel. ext. (k=2) Measurement Uncertainty | ≥1·10-4 | |
Measuring Conditions | 1 pF up to 10000 pF For Low-Voltage: For High-Voltage:
|
Calibrator for Instrument Transformer Test Sets

Short Name | MAV III | |
Principle | Comparision Method | |
rel. ext. (k=2) Measurement Uncertainty | 10 ppm up to 100 ppm 10 µrad up to 100 µrad | |
Measuring Conditions | 0.01 A up to 10 A
|
Current Transformer Calibration System

Short Name | SEKAM II | |
Principle | Comparision Method | |
rel. ext. (k=2) Measurement Uncertainty | 2 µA/A up to 30 µA/A 2 µrad up to 50 µrad | |
Measuring Conditions | 0.05 A up to 100 kA
|
Voltage Transformer Calibration System

Short Name | ESM II | |
Principle | Comparison Method | |
rel. ext. (k=2) Measurement Uncertainty | 2 µV/V up to 100 µV/V 2 µrad up to 50 µrad | |
Measuring Conditions | 30 V up to 300 kV
|
Standard Burden Calibration System

Short Name | BME II | |
Principle | Impedance Measurement | |
rel. ext. (k=2) Measurement Uncertainty | 0,1 % up to 1 % 0,1 crad up to 1 crad | |
Measuring Conditions | 0,025 A up to 10 A
|